Utilization category |
Typical application[2][3] |
Applicable IEC norm[3]
|
AC-1 |
Non-inductive or slightly inductive loads, example: resistive furnaces, heaters |
60947-4-1
|
AC-2 |
Slip-ring motors: switching off |
60947-4-1
|
AC-3 |
Squirrel-cage motors: starting, switches off motors during running time |
60947-4-1
|
AC-4 |
Squirrel-cage motors: starting, plugging, inching |
60947-4-1
|
AC-5a |
Switching of discharge lamps |
60947-4-1
|
AC-5b |
Switching of incandescent lamps |
60947-4-1
|
AC-6a |
Switching of transformers |
60947-4-1
|
AC-6b |
Switching of capacitor banks |
60947-4-1
|
AC-7a |
Slightly inductive loads in household appliances: examples: mixers, blenders |
60947-4-1 61095
|
AC-7b |
Motor-loads for household appliances: examples: fans, central vacuum |
60947-4-1 61095
|
AC-8a |
Hermetic refrigerant compressor motor control with manual resetting overloads |
60947-4-1
|
AC-8b |
Hermetic refrigerant compressor motor control with automatic resetting overloads |
60947-4-1
|
AC-12 |
Control of resistive loads and solid state loads with opto-coupler isolation |
60947-5-2
|
AC-13 |
Control of solid state loads with transformer isolation |
60947-5-1
|
AC-14 |
Control of small electromagnetic loads |
60947-5-1
|
AC-15 |
Control of A.C. electromagnetic loads |
60947-5-1
|
AC-20 |
Connecting and disconnecting under no-load conditions |
60947-3
|
AC-21 |
Switching of resistive loads, including moderate overloads |
60947-3
|
AC-22 |
Switching of mixed resistive and inductive loads, including moderate overloads |
60947-3
|
AC-23 |
Switching of motor loads or other highly inductive loads |
60947-3
|
AC-31A AC-31B ³)
|
Non-inductive or weakly inductive loads
|
60947-6-1
|
AC-33A AC33B³)
|
Motor loads or mixed loads including motors, resistors and up to 30% incandescent lamp load
|
60947-6-1
|
AC-35A AC-35B ³)
|
Gas discharge lamp load
|
60947-6-1
|
AC-36A AC36B ³)
|
Incandescent lamp load
|
60947-6-1
|
AC-40
|
Distribution circuits of mixed resistive and inductive loads
|
60947-6-2
|
AC-41
|
Non-inductive or weakly inductive loads, resistance furnaces
|
60947-6-2
|
AC-42
|
Slip ring motors: Starting, switching off
|
60947-6-2
|
AC-43
|
Squirrel cage motors: Starting, switching off during operation
|
60947-6-2
|
AC-44
|
Squirrel cage motors: Starting, counter-current braking ¹) or reversing ¹), typing ²)
|
60947-6-2
|
AC-45a
|
Switching of gas discharge lamps
|
60947-6-2
|
AC-45b
|
Switching incandescent lamps
|
60947-6-2
|
AC-51
|
Induction-free or slightly inductive loads, resistance furnaces
|
60947-4-3
|
AC-52a
|
Control of the stator winding of a slip-ring motor: 8-hour operation with starting currents for starting processes, maneuvering, operation
|
60947-4-2
|
AC-52b
|
Control of the stator winding of a slip ring motor: Intermittent operation
|
60947-4-2
|
AC-53a
|
Control of a squirrel cage motor: 8-hour operation with starting currents for starting processes, maneuvering, operation
|
60947-4-2
|
AC-53b
|
Control of a squirrel cage motor: Intermittent operation
|
60947-4-2
|
AC-55a
|
Switching of electrical controls of discharge lamps
|
60947-4-3
|
AC-55b
|
Switching incandescent lamps
|
60947-4-3
|
AC-56a
|
Switching transformers
|
60947-4-3
|
AC-56b
|
Switching of capacitor batteries
|
60947-4-3
|
AC-58a
|
Control of a hermetically sealed refrigeration compressor motor with automatic reset of overload releases: 8-hour operation with starting currents for starting, maneuvering, operation
|
60947-4-2
|
AC-58b
|
The control of a hermetically sealed refrigeration compressor motor with automatic reset of the overload trips: Intermittent operation
|
60947-4-2
|
AC-140
|
Control of small electromagnetic loads with holding current ≤ 0.2 A; e.g. contactor relays
|
60947-5-2
|
A |
Protection of circuits, with no rated short-time withstand current |
60947-3
|
B |
Protection of circuits, with a rated short-time withstand current |
60947-3
|
DC-1 |
Non Inductive or slightly inductive loads, resistance furnaces, heaters |
60947-4-1
|
DC-3 |
Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors |
60947-4-1
|
DC-5 |
Series-motors, starting, plugging(1), inching(2), dynamic braking of motors |
60947-4-1
|
DC-6 |
Switching of incandescent lamps |
60947-4-1
|
DC-12 |
Control of resistive loads and solid state loads with opto-coupler isolation |
60947-5-1 60947-5-2
|
DC-13 |
Control of D.C. electromagnetics |
60947-5-1 60947-5-2
|
DC-14 |
Control of D.C. electromagnetic loads having economy resistors in the circuit |
60947-5-1
|
DC-20 |
Connecting and disconnecting under no-load conditions |
60947-5-1
|
DC-21 |
Switching of resistive loads, including moderate overloads |
60947-5-1
|
DC-22 |
Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) |
60947-5-1
|
DC-23 |
Switching of highly inductive loads (i.e. series motors) |
60947-5-1
|